Welcom to Visit TingWall Inc.
A Revolution in Cutainwall Technology
 
  About TingWall
  News
  Products
  Projects
  Testing
  Technical Papers
  TingWall's Bulletins
  Affiliates
  Patents
   
   
   
   
   
   
   
Our Testing Stories

Two-story China Mock-up Test in China, 2002

A two story high, full scale TingWall™ mock-up was tested on October 22 and October 23 of 2002 at the Chinese government laboratory in Guangzhou in accordance with the requirements of Chinese Curtain Wall Standard GB/T 15227-94. The test results indicated that the performances are either the Top Grade or beyond the Standard requirement as itemized below in accordance with the sequence of tests.



  • Air Leakage Rate Tests


  • The air leakage rates were recorded at load stages of 10 Pa, 20 Pa, 30 Pa, 50 Pa, 70 Pa, 100 Pa, 150 Pa (3.14 psf), 100 Pa, 70 Pa, 50 Pa, 30 Pa, 20 Pa, 10 Pa. All the recorded air leakage rates are well within the maximum allowable limit achieving the Top Grade in accordance with the Chinese Standard. For the purpose of comparison, in the USA, the AAMA recommended load for Air Test is between 1.6 psf and 6.4 psf.

  • Static Water Test


  • Non-stop water tests were conducted at five elevated load stages with 10 minutes duration at each load stage. The five load stages are 500 Pa or 10.5 psf, 700 Pa or 14.7 psf, 1,000 Pa or 21 psf, 1,600 Pa or 33.5 psf and 2,500 Pa or 52.4 psf. There was no water leakage up to the final stage of 2,500 Pa for a total duration of 50 minutes achieving the Top Grade in accordance with the Chinese Standard. For the purpose of comparison, in the USA, the AAMA recommended maximum load for water test is 12 psf and the test duration is 15 minutes. The Chinese requirements are much more severe than USA in both pressure and duration.

  • Structural Wind Load Tests


  • The tests were conducted in load stages up to the design wind load of +3,000 Pa (62.9 psf) and -4,600 Pa -96.4 psf). The deflection data were recorded at each load stage. The test results indicated that all the deflection data were well within the allowable limit.

  • Story Drift (Seismic) Tests


  • The maximum Chinese requirement for the test is story height/100 (L/100). After the L/100 test, the curtain wall system is allowed to fail and the only requirement is no broken components falling off the mock-up. The test results indicated no damage to the TingWall™ system at all.

  • Water Tests with Pulsatory Pressures


  • In accordance with the Chinese Standard, there is no need for conducting water test after the L/100 Story Drift Tests. Therefore, this test represents the condition of beyond the Standard. There was no water leakage up to a maximum pulsatory pressure of 1,600 Pa or 33.5 psf.

  • Wind Overload Tests


  • The maximum load of +4,500 Pa (94.3 psf) and -6,400 Pa (-134.2 psf) were applied to the mock-up and the curtain wall system is allowed to fail with the only requirement of no broken components falling off the mock-up. The test results indicated no damage to the TingWall™ system at all.



    The mock-up structure was disassembled and shipped to Japan for re-assembling and re-tests in accordance with the Japanese Building Standard scheduled in March 2003. To re-test a mock-up after sustaining the theoretical ultimate load tests (Story Drift at L/100 and Wind Overload at -6,400 Pa) is extremely unusual - indeed this may be the first in the history of curtain wall performance testing. A successful re-test would strongly indicate the non-destructive nature and the long-term performance nature of the TingWall™ system.
     
     
     
     
    Other Stories
    Three-story mock-up test in Taiwan, 1997
    Two-story mock-up test for Kossman Development Co. -for Omega Corporate Center
    Building sidesway due to wind and seismic forces
    Fastener load due to negative wind pressure
    Dead-Loaded Mullion / Floor Hanging Mullion
    Two-story mock-up test at Architectural Testing Inc., 1994
    Small-scale water test in Taiwan, 1995
     
     
     
      Some of products shown may be protected by one or more of the following U.S. Patents 5,452,552; 5,596,851; 5,598,671; 5,687,524, and foreign patents based on these U.S. patents. In addition, other related patents are pending. Rights to these patents are owned by Advanced Building Systems, Inc., Wilmington, DE, a wholly-owned subsidiary of TingWall Inc.