Welcom to Visit TingWall Inc.
A Revolution in Cutainwall Technology
 
  有關 TingWall™
  新聞發佈
  系統介紹
  工程實績
  測試成果
  技術文件
  TingWall 簡報
  合作夥伴
  專利權
   
   
   
   
   
   
   
SOLUTIONS TO CURTAIN WALL PROBLEMS USING AIRLOOP SYSTEM PDF version
Written By Raymond Ting

The purposes of providing a curtain wall on a building are to provide the aesthetic character of the building skin and to protect the building interior from the effects of natural phenomena including sunlight exposure, wind, rain, earthquake, and temperature. Various facing materials have been utilized in the curtain wall construction such as glass, stone, aluminum plate, aluminum composite plate, steel plate, and composite foam panel etc.

To complete the exterior building skin, many pieces of facing panels must be joined together and sealed against air and water infiltration. The majority of the curtain wall problems is related to the panel joint design.

Due to the multiple performance functions required for the curtain wall system design, it has been a long struggle in the industry for trying to provide an enduring system to fulfill all performance functions. The curtain wall design work is further complicated by the interactions among the various performance functions, for example, the best solution for a particular performance function may be detrimental to the other performance functions.

The major curtain wall problems & their solutions using Airloop System are listed below:

1. Problems Induced by Water Leakage:

Due to zero tolerance requirements is required for this problem, it has been a constant struggle in the industry to provide a system with long lasting water tightness performance. The difficulty of providing a long lasting watertight system is due to the difficulty of maintaining long lasting sealant integrity at the "Critical Seal Locations".

A "Critical Seal Location" is defined as any location that requires a perfect seal to prevent water leakage. The "Critical Seal Location" is required if the location is required to simultaneously seal both air and water. Sealant failures are caused by sealant stress fatigue and/or sealant material degradation. The problems induced by water leakage include the interior water damage, the loss of insulation value due to the wetting of the insulation material, and the sick air building problem due to the growing of toxic molds in the wall cavity.

Attempting to solve this problem in recent years, methods of implementing "Rain Screen Principle" have been widely accepted in the industry. The "Rain Screen Principle" is an attempt to nullify the wind force that causes the water infiltration. However, due to the fact that the horizontal joint cavity is blocked off at the ends by the vertical frame or support member, the pressure equalization mechanism would by disabled when the water running along the surface of the curtain wall starts to blanket over the air entry horizontal joint gap. In addition, the member joint and fastener holes at the horizontal/vertical juncture remain to be "Critical Seal Locations".

Therefore, the "Rain Screen Principle" does not completely solve the long term water leakage problem. The long term water leakage problem is solved by the "Airloop System" by eliminating all "Critical Seal Locations" in the system as explained as follows with reference to figures 1 and 2. In the ":Airloop System", all sealant lines can be classified into two groups, namely, 1) "Water Seal" which is located between the exterior water path and the pressure equalized dry outer or inner "Airloop" and 2) "Air Seal" which is located away from the exterior water path and along the interior border of the pressure equalized dry outer or inner "Airloop".

In the "Airloop System", typically each rectangular facing panel is shop assembled and sealed to one top "Airloop" member, two vertical "Airloop" members, and one bottom "Airloop" member. The "Airloop" members are miter-matched at the corners to form a complete "Inner Airloop". After the panels have been erected to form the curtain wall, the cavities in the vertical panel joints are connected with the cavities in the horizontal panel joints forming the "Outer Airloop" around each panel. The "Outer Airloop" is separated into two segments.

The first segment (1st OAL on Figures 1 & 2) is utilized for instantaneous water drainage and air entry into the "Inner Airloop". The second segment (2nd OAL on Figures 1 & 2) is the dry "Outer Airloop" to protect the panel joint and support "Air Seals". In this arrangement, the "Water Seals" including the miter joint seals are completely separated from the "Air Seals" eliminating all "Critical Seal Location" and pressure equalization mechanism will not be disabled due to water blanketing over the horizontal panel joint since air can freely feed into the "Outer Airloop" from the vertical panel joint.

Therefore, all the drawbacks of the "Rain Screen Principle" are eliminated in the "Airloop System" and long term water tightness performance is ensured.

2. Problems Induced by Interfloor Story Drift due to Wind Load or Earthquake:

In the conventional "Stick" or "Unitized" curtain wall systems, the inside parts of the sealant lines around the facing panel (e.g. glass, aluminum plate, stone, etc.) are also the sealant lines on the panel supporting mullion and girt.

In the event of inter-floor story drift, the supporting mullion which is attached to the floor structure would be laterally shifted with the floor forcing the panel to change from the original rectangular shape into a non-rectangular parallelogram as shown on Figure 3.

The inherent high in-plan shear stiffness of the facing panel in resisting the in-plan shear distortion would force the sealant lines to absorb the majority of the shear distortion. Stress fatigue on the sealant lines due to the effect of repeated inter-floor story drifts would cause bond shear failure of a caulked sealant line and eventually cause the sealant material to walk out of the sealing pocket. Falling cured caulking strings or gaskets are normally caused by this problem.

If the sealant failure occurs at the "Critical Seal Location", it would cause the water leakage problem. If there is inadequate horizontal clearance between the adjacent facing panels to absorb the inter-floor story drift, it would result in the structural failure of the facing panel such as panel buckling in metal panel or broken glass falling from the sky.

In the "Airloop System", both the structural and sealant stress problems are eliminated as explained as follows: Each facing panel is supported by two screws at the top corners and structurally engaged at the bottom against forces perpendicular to the panel surface with no restraint against lateral sliding and the vertical segment of the "Outer Airloop" provides the clearance (Dimension C in figure 2) for lateral horizontal joint sliding.

Therefore, the total story drift can be designed to be absorbed by stepwise stress-free panel drifts as shown in Figure 4. The panel distortion analysis are illustrated below.

Design Story Drift = D (mm or in)
Story Height = L (mm or in)
Stress-free Panel Drift = B (mm or in)
Outer Airloop Clearance = C (mm or in)
Panel Height = H (mm or in)
The following relationship exist is a stress-free panel drift condition.
B/H = D/L
Solving the above equation for B yields:
B = D H / L-------------------------------------------------------------(1)
If C > B, the "Airloop System" undergoes stress-free panel drift. It can be seen from Equation (1) that for a known floor height, a stress-free panel drift design can always be accomplished by reducing H and/or D.
If C < B, the "Airloop System" would undergo a reduced panel distortion, R, as measured by the following equation:
R = (B – C) / H---------------------------------------------------------(2)


For a conventional "Stick" or "Unitized" system, C = O in Equation (2), therefore, the panel distortion in the system is always much higher than that in the "Airloop System". Due to the experience of earthquake damage, in addition to the elastic story drift requirement for the design seismic load, the U.S.

Building Codes have changed dramatically to require a high allowable inelastic story drift for absorbing the earthquake energy in the building design for the factored seismic load. For example, in 1991 & 1994 UBC (Uniform Building Code), the maximum allowable elastic story drift is L/200 (L = floor height) for structures having a fundamental period of less than 0.7 second. In 1997 UBC, the additional parameter of maximum allowable inelastic story drift is L/40.

In response to this Code change, it seems to be reasonable to establish the following two parameters for the curtain wall design. (1). The curtain wall system shall be designed for no damage or permanent deformation under the effect of the actual elastic story drift for design seismic load. (2). The curtain wall system shall be designed as the ultimate load condition under the effect of the inelastic story drift for the factored seismic load.

In the "Airloop System", the problem of sealant stress fatigue can be easily eliminated by designing a stress-free panel drift condition for the elastic story drift. Under the effect of the inelastic story drift, the curtain wall responses in the "Airloop System" can be explained in the following three stages.

Stage 1: Stress-free panel drift up to the point that the outer Airloop clearance (dimension "C") is completely exhausted.

Stage 2: Sealant stress built-up up to the point that the inner Airloop clearance is completely exhausted.
Stage 3: In-plan shear stress built-up within the facing panel until the facing panel reaches the ultimate failure point.

For comparison purposes, the following numerical calculations are provided using 1997 UBC with the assumption of L/200 for the elastic story drift and L/40 for the inelastic story drift.

Item Stick or Unitized Airloop System
C = 8 mm C=20mm* (1)
L 3600 mm 3600 mm 3600 mm
D (elas.) 18 mm 18 mm 18 mm
D (inelas.) 90 mm 90 mm 90 mm
H 1500 mm 1500 mm 1500 mm
C 0 mm 8 mm 20 mm
B 37.5 mm 37.5 mm 37.5 mm
R (Stage 1) 0.002 0 0
R 0.005 0.0028*(2) 0
R 0.025 N.A. 0.012*(3)

* (1). Outer Airloop clearance = 8 mm;
   Inner Airloop clearance = 12 mm;
   Total Airloop clearance = 20 mm.
* (2). Sealant stress condition.
* (3). Panel stress.

The above example illustrates that the "Airloop System" can be easily designed for a sealant stress-free condition for the elastic story drift and the panel distortion in the ultimate condition is much less than that in the "Stick" or "Unitized" system.

3. Problems Induced by Cyclic Wind Loads:

In a conventional curtain wall system ("Stick" or "Unitized"), the load transferring mechanisms for the wind loads perpendicular to the panel surface are explained as follows.

There are three steps in load transferring mechanism for the positive wind loads as explained as follows:

(1). The loads on the panel surface are distributed into the horizontal and vertical supports by bearing reactions around the panel edges.(2). The bearing reactions on the horizontal supports are transferred into the vertical support through fasteners at the ends of the horizontal support. (3).

The total loads on the vertical support are then transferred into the building floor structure through the floor connection system. There are also three steps in load transferring mechanism for the negative wind loads as explained as follows.

(1). The loads on the panel surface are transferred into the exterior panel frame members through fasteners connecting the panel frame members to the vertical and horizontal supports. (2). The loads on the horizontal supports are transferred into the vertical support through fasteners at the ends of the horizontal support. (3). The total loads on the vertical support are then transferred into the building floor structure through the floor connection system.

In Step (2) for positive wind and steps (1) & (2) for negative wind, screws are commonly used for the connection. Under the effects of repeated positive and negative wind load cycles, the screws would eventually become loose to induce the water leakage problem if the screw holds are located at the "Critical Seal Locations".

In more severe condition, the screws could be totally disengaged causing major structural failure of flying curtain wall phenomenon. In the "Airloop System", the above problems are eliminated by the system design arrangements as explained as follows (see Figure 5). (1).The panel is structurally captured inside the vertical support as shown in Figure 5. Therefore, both positive and negative wind loads on the facing panel are directly transferred into the vertical support without going through the panel fastener. To erect the panel, the panel can be easily placed into the engaged position by wiggling actions. (2). All fastener holes are not in the "Critical Seal Location" and in fact, they are connecting between two pressure equalized spaces. (3). In this manner, the fasteners are being utilized to support the panel weight only.

4. Workmanship Problem:

In the conventional "Stick" or "unitized" system, the panel joint formation and sealing details varies with the facing panel material plus the variations of horizontal and vertical joints, the joint formation and sealing procedures involves many variations. For example, if three facing materials (e.g. vision glass, spandrel glass, and aluminum plate) are used on a building, there are a total of twelve different joint formation and sealing procedures (6 for horizontal joint and 6 for vertical joint) for a simple flat curtain wall. Regardless of whether the joint formation and sealing details are executed in the field (Stick System) or in the shop (Unitized System), unintentional mistakes are likely to occur due to the worker's lack of memory in so many different execution procedures. In the "Airloop System", the above problem is eliminated due to the following three reasons. (1). Each type of facing material has one framing and sealing procedures in the shop while there is only one field joint formation and sealing procedures for all different facing materials (universal field joint). (2). There is no "Critical Seal Location" in the "Airloop System". (3). The load transferring mechanism in the "Airloop System" relies on mechanical interlocks rather than fasteners applied by the worker.

5. Long Term Aesthetic Performance Problem:

In a wet sealed system using exposed silicone caulking, the problems of streaking and dirt collection along the caulked joints have become a serious concern in the industry. In an internal gutter system, water stains would form below the drainage holes due to the delayed drainage mechanism. In the "Airloop System", this problem is eliminated since all the panel joints are open without caulking and the water drainage mechanism is instantaneous.

6. Problems with Exterior Fixtures:

There are many exterior fixtures desirable to the design architect or building owner such as decorative vertical or horizontal fins, sun screen, window washing hocks, building sign or symbol, and special ornament. These exterior fixtures are protruding out of the curtain wall surface and must be structurally supported. In the conventional "Stick" or "Unitized" system, the structural support for the exterior fixtures often involves penetrations of the curtain wall and/or disruptions of the water sealing details. Therefore, the exterior fixtures often cause undesirable structural effects or water leakage problem. In the "Airloop System", the above problems are eliminated as explained as follows. An extruded connection clip can be secured to the "Airloop Mullion Head" anywhere along the length of the mullion to provide an anchoring point for any type of support system for the exterior fixtures as show in Figure 6. In this manner, there is no penetration of the curtain wall, no effect on the sealing integrity of the curtain wall.

7. Problems with Curtain Wall Renovation:

The idea of a curtain wall renovation project is to improve the performance parameters including aesthetic, structural, thermal, air/water tightness, or the combinations thereof. Therefore, the system details for the renovation are normally different from the existing curtain wall. For a conventional "Stick" or "Unitized" system, a renovation project normally requires a complete stop of building interior operations due to the following reasons. (1). The scope of work requires the removal of the existing curtain wall panels and supports and the installation of new supports and panels, therefore, at the end of each field working day, there will be a building hole and the problem of protecting the building hole against weather and vandalism during the non-working hours or days becomes a major project killing factor. (2). In most cases, the interior wall and many interior fixtures are attached to the existing curtain wall supports, therefore, replacing the existing curtain wall supports with new supports would require massive restoration of interior wall and fixtures. In most cases, the cost becomes the prohibitive factor for the renovation project. (3). Even if the above two problems are overcome with money and phased renovations, the curtain wall erection must be proceeded in a predetermined sequential direction. This requirement might become impossible for keeping continuous interior operations.

In the "Airloop System", the above problems are eliminated as explained as follows. (1). Uniquely designed adapting extrusions for any specific existing mullion can be secured to the sides of the existing mullion to convert the existing mullion into the "Airloop Mullion", therefore, there is no need for replacing the existing mullions and the problems of building hole and massive interior restoration are eliminated. (2). The "Airloop Panels" are placed into position by wiggling action between two mullions, therefore, the erection is non-directional and the renovation can be executed in any non-sequential manners.

A major curtain wall renovation project for the IBM plant in Rochester, MN with an estimated 800,000 square foot of curtain wall has been awarded using "Airloop System" and tentatively scheduled to be phased in 10 years with the first phase to be completed in October 2000. The cross-section of the renovated mullion is shown in Figure 7. Aluma Tech / Pacific of Tualatin, Oregon is the "Airloop Panel" supplier for the project and Ford-Metro Glass of Rochester, MN is the erector for the project.

8. Problems caused by Vertical Structural Movements:

The vertical structural movements include thermal expansion or contraction of the curtain wall components and the differential inter-floor deflection (DID). In most cases, the DID is a major design consideration for the curtain wall system. Similar to other wall systems, the "Airloop System" can be used with a dead-loaded mullion with slotted mullion connection clip to absorb the DID (normally in low-rise) or a floor hanging mullion system (normally in high-rise) with flexible panel joint and mullion spliced joint to absorb the DID.

To prevent the failure of the sealing properties (air and/or water at the mullion spliced joint, it is desirable to limit the DID as much as possible. A maximum spandrel beam deflection of + 3/8" is found to be practical for most curtain wall systems including the "Airloop System".

In case of thermal movements, the "Airloop System" has a unique advantageous behavior as explained a follows: (1). The engaged horizontal panel joint has a gap which is more than adequate to allow unrestrained vertical thermal movements of the panel. (2). The "Airloop Panel" is fastened to the mullion near the interior face which is subjected to only minor temperature changes while the outer face of the panel vertical frame can undergo near unrestrained rotation and horizontal movements within the "Outer Airloop" space to absorb the horizontal thermal movements of the facing panel.

Therefore, the common problem of face wrinkling of long metal panel in the conventional "Stick" or "Unitized" system is eliminated in the "Airloop System".

The Phase I of a project named Omega Corporate Center (about 80,000 square foot of curtain wall) near Pittsburgh, PA has been completed since October 1999 with "Airloop Panels" of exposed frame vision glass, exposed frame spandrel glass, and hidden frame aluminum plate system. Many long aluminum plates (max. 3' 8" by 26') are utilized and excellent surface flatness is maintained in cold or hot under the sun (see Photos 1 to 3).

The Phase II project is now under construction. The project owner is Kossman Development Company, Pittsburgh, PA and the panel supplier & erector is EPI Wall Systems, Pittsburgh, PA.

9. Maintenance Problems:

In the conventional "Stick" or "Unitized" system, replacing facing material such as glass or plate often require to work form both outdoor and indoor and very time consuming and replacing panel frame members damaged by air born missiles is even more difficult.

In the "Airloop System", replacing damaged glass can be done easily from the indoor for a vision glass and from the outdoor for a spandrel glass and each individual panel can be replaced with minimum effort by dropping two panels below to provide room for the replacement work.

In the case of the March 2000 massive tornado damages to the curtain walls in downtown Fortworth, TX, should the curtain wall be the "Airloop System", the required time to repair the curtain wall is estimated to be less than 50% of the time required for the conventional "Stick" or "Unitized" system.

10. Problem of Interior Water Condensation:

When the interior surfaces temperature of a curtain wall component is below the dew point of the interior air environment, water condensation will form on that interior curtain wall surface. Similar to other curtain wall systems, to improve the condensation resistance factor (CRF), various thermal break methods can be utilized in the panel frames of the "Airloop System" as shown in Figure 8.

Due to the fact that the ratio of the interior mass to the exterior mass of the "Airloop Mullion" as shown in Figure 8 is much larger than that of the panel frame, the CRF of the "Airloop Mullion" is expected to be higher than that of the "Airloop Panel Frame" without thermal break, therefore, it is preferred not to use thermal break on the mullion if its CRF is adequate since the use of thermal break would reduce the structural strength of the mullion. However, if it is necessary, thermal break can be utilized in the "Airloop Mullion" as shown in Figure 9.

It is believed that the unusually high volume of air trapped in the joints of the "Airloop system" would provide additional insulation value to increase the CRF value as compared to the conventional "Stick" or "Unitized" system. This has been indicated by the result of the CRF test on the "Airloop System" conducted at Architectural 測試成果 Inc., York, PA as shown below. Test Temperatures: Indoor = 67.9F; Outdoor = 18F CRF Values: Frame = 58; Glass (1" insulated) = 45.

11. Problem with Long Term Air Tightness Performance.

The degradation of the air tightness performance is due to the loosening or bond failure of the air seals under the effect of various cyclic structural movements (most critical in the story drift movement) within the curtain wall system. This problem is typical in the conventional "Stick" or "Unitized" system. In the "Airloop System", this problem is either eliminated or minimized due to the following two reasons: (1). As explained in Item 2 above, the story drift movement does not produce sealant stress in the "Airloop Panel", therefore, loosening of the panel air seal is unlikely. (2). Compressive type of dry air seal is used for the support air seal to allow free sliding between the panel frame and the support, therefore, the problem of sealant bond failure is eliminated.

The extraordinary water tightness performance of the "Airloop System" has been repeatedly demonstrated in two very unusual mock-up tests conducted at Farabaugh Engineering & 測試成果, Inc., Turtle Creek, PA as summarized below.

(1). Kossman Mock-up: two story high; mixed horizontal and vertical support systems; three types of panels (exposed frame vision glass, exposed frame spandrel glass and hidden frame aluminum plate); mixed ASTM E-283 air test, ASTM E-331 water test, ASTM E-330 structural test, and building side sway test.

a. Over more than a one year period, the same mock-up has been tested ten time with the mixed tests and the very unusual water test procedures. The mock-up has not been repaired or modifies. The result was no water leakage each time.
b. Test duration up to 45 minutes as compared to the standard 15 minutes.
c. Test pressure up to 20 psf compared to the AAMA recommended maximum of 12 psf.
d. During the water test, a marriage seal was intentionally destroyed to demonstrate the tolerance of imperfect seal without causing water leakage.

The high degree of long term air tightness performance has also been demonstrated in the test results of this mock-up. The air leakage rate at 12 psf pressure varied within a narrow range with a mean of about 0.01 cfm per square foot of wall (which is much better than the AAMA recommended maximum air leakage rate of 0.06 cfm per square foot of wall) among the ten test indicating no performance degradation under repeated structural test, over more than a one year period.

(2). IBM Mock-up: two story high; vertical support system with existing mullions and renovation details; two types of panels (exposed frame vision glass & exposed frame aluminum composite plate with thermally broken frame); mixed ASTM E-283 air test, ASTM E-331 water test and ASTM E-? water test.

a. Over more than three a month period, the same mock-up has been tested three time with the mixed tests and the very unusual water test procedures. The mock-up has not been repaired or modified. The result was no water leakage each time.
b. In order to demonstrate the extraordinary high degree of imperfect seal tolerance, severe air leakage rate (0.264 cfm per square foot of wall area at 5.2 psf) was intentionally introduced in the erection of the mock-up.
c. Test duration up to 30 min. as compared to the standard 15 min.
d. Test pressure up to 15 psf as compared to the AAMA recommended maximum of 12 psf.

In order to demonstrate the structural strength of the "Airloop System" against the negative wind load, a separate structural mock-up test using the system for the IBM renovation project was conducted. The mock-up used a vision glass panel of 4 foot by 4 foot and an Alpolic panel of 4 foot wide by 7 foot high. An ultimate negative load of 150 psf was recorded with the failure mode of Alpolic panel being pulled out from the gazing pocket along one of the 7 foot long side. A fastener or "Airloop" frame distress was observed. This proved out the mechanism of direct load transfer into the mullion with no connection stress.

In summary, the "Airloop system" offers an unprecedented degree of imperfect seal tolerance without causing the water leakage problem ensuring a long term water tightness performance. In addition, the improvements in the various structural performance parameter are also very significant. It is believed that there exists a limit between the water tightness performance and the degree of imperfect seal. However, this limit in the future research by increasing the water test pressure and/or the air leakage rate in the system.

Even though the "Airloop System" seems to have provided solutions to most of the curtain wall problems, nothing is perfect in this world. It is hoped that this paper would generate more discussions in the industry to further the "Airloop" technology. For reference to the inception of the "Airloop" technology, the following papers published by this writer would be helpful.

1. "Evolution of Curtain Wall Design Against Water Infiltration" Metal Architecture, January & February 1997.
2 "Evolution of Curtain Wall Design Against Water Infiltration", Proceedings, International Conference on Building Envelope Systems & Technology, Bath, U.K., April 1997.
3. "Curtainwall Design Evolution" Glass Magazine, April 1998.



 
 
 
 
其他文件
EVOLUTION OF CURTAIN WALL DESIGN AGAINST WATER INFILTRATION
STORY ABOUT TINGWALL SOLVING THE MOLD PROBLEM
CURTAIN WALL PERFORMANCES: LABORATORY VS. REAL BUILDING
CURTAIN WALL DESIGN AGAINST STORY DRIFT
氣環式幕牆易被誤解特性的說明
 
 
 
  部分產品由以下美國及世界各地專利權保護 - U.S. 專利權 5,452,552; 5,596,851; 5,598,671; 5,687,524. 除此之外, 更有多項專利正在申請中. 此些專利權均由丁氏幕牆100%擁有之子公司, Advanced Building Systems, Inc.,Wilmington, DE 所有.